EnergyPlus Doc1

Required at run time

  • Weather file (EPW): EPW_PATH (absolute path you pass to the CLI).
  • EnergyPlus executable: EPLUS_EXE (path to …/energyplus or just energyplus if on PATH).

Coupling inputs (only when the plugin is enabled)

out/exchange/coupling_in.json — the only external knobs your OpenFOAM side sets each timestep:

  • T_supply_C (float): supply air temperature setpoint (°C).
  • m_dot_kg_s (float): supply mass flow rate (kg/s).
  • Example: { “T_supply_C”: 16.0, “m_dot_kg_s”: 0.30 }

Control circle

Supply path: supply_in → OA System → mixed_air → DX → cool_out → ElecHeat → heat_out → Fan → fan_out

Demand path: fan_out → ZoneSplitter → term_in → Terminal → zone_in → (Zone) → zone_ret → ZoneMixer → supply_in

Model-internal parameters (set in the script)

Geometry & zone

  • Room size: 5 m × 4 m × 3 m (volume used for ACH).
  • Surfaces: 4 walls, roof, floor (simple single-layer construction).
  • Global rules: vertex order/coordinate system (GlobalGeometryRules).

Schedules (simple constants)

Always On (1.0).

  • SAT 13C (13 °C scheduled supply-air temperature).
  • MinOAFrac 0.2 (used by the OA controller).

HVAC topology & components

  • OutdoorAirSystem with Controller:OutdoorAir (economizer off; min/max OA flow = 0 / Autosize).
  • DX cooling coil (single speed) with condenser air OutdoorAir:Node.
  • Electric heating coil.
  • Fan:SystemModel (autosized flow; basic power/per-flow setting).
  • Air terminal: AirTerminal:SingleDuct:Uncontrolled (single zone).
  • Zone Splitter → terminal inlet; Zone Mixer ← zone return.

Setpoint Managers

  • Scheduled 13 °C on the supply outlet node.
  • MixedAir manager to make the coils “see” that SAT before the fan.

Sizing (autosize drivers)

  • Sizing:Zone: supply design temps (13 °C cooling, 40 °C heating), humidity ratios (0.008).
  • Sizing:System: central SATs, plus required preheat/precool temperatures & humidity ratios.

Site & simulation control

  • Site:Location (generic numbers in the script; actual weather comes from EPW).

  • RunPeriod (Jan 1–2), Timestep (6 per hour), Version.

Building (solar distribution etc.).

Diagnostics (optional: display warnings/extras if you included that block).

Curves

Flat performance curves for DX coil capacity/EIR and PLF (all coefficients = 0 except constant = 1).